Description
- 95W Output Power
- 187-265V AC Voltage (50Hz)
- High Efficiency
- Natural Cooling
- Low Ripple and Noise
- Easy Connection
- Power and Fault Indicator LEDs
- Battery Temperature Compensation
- Constant Current Battery Charger (C/10)
- Optional Serial Output and Software
- EN54-4 approved
| electrical | |||
| Entrance | |||
| Nominal Voltage (Operating Voltage) | 187V – 265V AC | ||
| Frequency | 50Hz | ||
| Input Current | <1A at full load | ||
| Inrush Current | 5A max. 25 °C 220V AC 10ms | ||
| Insurance | F2A 20mm, 250V AC Glass | ||
| Network | F2A 20mm, 250V AC Glass | ||
| Exit | |||
At Full Load | Output Voltage | 26V – 28V DC (27.2V normal) | |
| Battery Voltage | 21V – 26V DC | ||
| Fluctuation | <250mV pk-pk max. | ||
| Battery | 7Ah | ||
Network | Load | T5A 20mm Glass | |
| Battery | T5A 20mm Glass | ||
Continuous Drawing Current | I max A Charged / Battery Empty | 3 a | |
| I max B No Charge / Battery Full | 3.5A | ||
| I min Current Drawn by the System / Load None | 32mA Ω 27.2V | ||
| Ri max. | 560mΩ | ||
| Communication | Optional RS232 | ||
| Battery | |||
| Battery Capacity | 2 x 7Ah | ||
| Battery Charging | 80% capacity in 24 hours with constant current 100% charge in 48 hours Economical charging Check every 24 hours (Battery Temperature Compensation) | ||
| Low Battery Threshold Voltage | 22V | ||
| Battery Final Voltage ( System shutdown voltage when operating on battery) | Threshold voltage - 21V | ||
| General | |||
| Material | Metal | ||
| Body Type | Standard | ||
| Colour | Black | ||
| Mains Cable Type | 0.75mm² | ||
| Battery Cable | 1.5mm² | ||
| Operating temperature | -10°C / +40°C | ||
| Storage Temperature | -20°C / +80°C | ||
| Enclosure Dimensions (HxWxD) | 404x404x87mm | 311x318x87mm | |
| Weight | 5.7kg | 4kg | |
| Certificates | |||
| Certificates | CE/ DEDAL | ||
| Approved organization number Dedal certificate number | 1922 1922-CPR-1691 | ||
| Standard number | EN 54-4 | ||
Reviews