Description
For use as a control and signal cable for computer systems and electronic control equipment. The screen provides protection against external noise, interference and signals.The dual helix structure allows the cable to retain its electrical capacity under intense electrical fields. Not for external or subterranean use.
Cable structure | |
Conductor | IEC 60228 S 5 TS/DIN EN 60228 CLASS 5 Twisted electrolytic copper |
Insulation | DIN VDE 0207 - YI2 PVC |
Stranding | Cores are twisted in layers at regular intervals |
Insulation Color Coding | DIN 47100 |
Seperetor | PES TAPE |
Screen | AL-PES tape with grounding wire |
Sheath | DIN VDE 0207 Bölüm 5 RAL 7032 |
Technicial Specifications | |
Conductor Resistance | 0.14 mm² = 148 Ω.Km |
0.22 mm² = 96 Ω.Km | |
0.25 mm² = 79.9 Ω.Km | |
0.34 mm² = 56 Ω.Km | |
0.50 mm² = 39 Ω.Km | |
0.75 mm² = 26 Ω.Km | |
1.00 mm² = 19.5 Ω.Km | |
1.50 mm² = 13.3 Ω.Km | |
2.50 mm² = 7.98 Ω.Km | |
Insulation Resistance | > 200 MΩ / Km |
Operating voltage | 0.14 mm² = 350 V |
≥ 0.22 mm² = 500 V | |
Test Voltage | 0.50 mm² < = 1500 V |
0.50 mm² ≥= 2000 V | |
Effective Capacity | 0.14 mm² = 90 nF/km |
0.22 mm² = 100 nF/km | |
0.25 mm² = 100 nF/km | |
0.34 mm² = 110 nF/km | |
0.50 mm² = 120 nF/km | |
0.75 mm² = 120 nF/km | |
1.00 mm² = 120 nF/km | |
1.50 mm² = 120 nF/km | |
2.50 mm² = 120 nF/km | |
Operating temperature | -30°C ~ +80°C |
Flame Test | IEC 60332-1-2 & EN 50265-2-1 |
min. Bending Radius | Fixed Fixed Laying 6,5 x D |
Movable Flexible 15 x D |
Reviews
Be the first to review this item
There are no reviews yet